11.12 T: Auto-Tuning
1036 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ T2-02: PM Motor Code Selection
No.
(Hex.)
Name Description
Default
(Range)
T2-02
(0751)
PM Motor Code
Selection
Sets the PM motor code for drives operating SMRA, SSR1, or SST4-series
Yaskawa PM motors.
Determined by A1-02
and o2-04
(0000 - FFFF)
Enter the motor code in T2-02 to automatically set parameters T2-03 to T2-14. When you are operating a
specialized motor or a non-Yaskawa motor designed, set T2-02 = FFFF and enter the data from the motor
nameplate or the motor test report.
You can only enter the permitted PM motor codes. Different drive control methods will accept different PM motor
codes.
■ T2-03: PM Motor Type
No.
(Hex.)
Name Description
Default
(Range)
T2-03
(0752)
PM Motor Type
Sets the type of PM motor the drive will operate.
1
(0, 1)
0 : IPM motor
1 : SPM motor
■ T2-04: PM Motor Rated Power
No.
(Hex.)
Name Description
Default
(Range)
T2-04
(0730)
PM Motor Rated
Power
Sets the rated output power (kW) of a PM motor.
Determined by o2-04
and C6-01
(0.00 - 650.00 kW)
Note:
Capacities 300 kW and less are set in units of 0.01 kW. Capacities above 300 kW are set in units of 0.1 kW. The maximum applicable
motor output varies depending on the setting of C6-01 [Normal / Heavy Duty Selection].
■ T2-05: PM Motor Rated Voltage
No.
(Hex.)
Name Description
Default
(Range)
T2-05
(0732)
PM Motor Rated
Voltage
Sets the rated voltage (V) of the motor.
200 V Class: 200.0 V,
400 V Class: 400.0 V
(200 V Class: 0.0 -
255.0 V, 400 V Class:
0.0 - 510.0 V)
■ T2-06: PM Motor Rated Current
No.
(Hex.)
Name Description
Default
(Range)
T2-06
(0733)
PM Motor Rated
Current
Sets the rated current (A) of the motor.
Determined by o2-04
(10% to 200% of the
drive rated current)
■ T2-07: PM Motor Base Frequency
No.
(Hex.)
Name Description
Default
(Range)
T2-07
(0753)
PM Motor Base
Frequency
Sets the base frequency (Hz) of the motor.
87.5 Hz
(0.0 - 590.0 Hz)