Standards Compliance
4
4.2 European Standards
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 243
Drive Model
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
2211
FWH-325A
FWH-450A
*1
2257 FWH-600A
2313 FWH-800A
2360 FWH-1000A
2415 FWH-1000A
*1 Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
Table 4.3 Factory-Recommended Branch Circuit Protection (400 V Class)
Drive Model
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
4002 FWH-50B
4004 FWH-50B
4005 FWH-50B
4007 FWH-60B
4009 FWH-60B
4012 FWH-60B
4018 FWH-80B
4023 FWH-90B
4031 FWH-150B
4038 FWH-200B
4044 FWH-200B
4060 FWH-225A
4075 FWH-250A
4089 FWH-275A
4103 FWH-275A
4140 FWH-300A
4168
FWH-325A
FWH-400A
*1
4208 FWH-500A
4250 FWH-600A
4296 FWH-700A
4371 FWH-800A
4389 FWH-1000A
4453 FWH-1200A
4568 FWH-1200A
4675
FWH-1400A
FWH-1600A
*1
*1 Yaskawa recommends a fuse with a large rated current for applications with repeated loads.
■ CE Standards Compliance for DC Power Supply Input
To comply with CE Standards, install a fuse for the DC power supply input.
Figure 4.3 shows a wiring example for a DC power supply that has two drives connected in parallel.