EasyManua.ls Logo

YASKAWA GA700 - Page 316

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.3 MEMOBUS/Modbus Communications
316 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Register No.
(Hex.)
Description
00C9
Minor Fault Description 3
bit 0 dEv [Speed Deviation]
bit 1 PGo [Encoder (PG) Feedback Loss]
bit 2 oPr [Keypad Connection Fault]
bit 3 CE [Modbus Communication Error]
bit 4 bUS [Option Communication Error]
bit 5 CALL [Serial Comm Transmission Error]
bit 6 oL1 [Motor Overload]
bit 7 oL2 [Drive Overloaded]
bit 8 Reserved
bit 9 EF0 [Option Card External Fault]
bit A rUn [Motor Switch during Run]
bit B Reserved
bit C CALL [Serial Comm Transmission Error]
bit D UL3 [Undertorque Detection 1]
bit E UL4 [Undertorque Detection 2]
bit F SE [Modbus Test Mode Error]
00CA
Minor Fault Description 4
bit 0 Reserved
bit 1 oH3 [Motor Overheat (PTC Input)]
bit 2 - 5 Reserved
bit 6 FbL [PID Feedback Loss]
bit 7 FbH [Excessive PID Feedback]
bit 8 Reserved
bit 9 dnE [Drive Disabled]
bit A PGoH [Encoder (PG) Hardware Fault]
bit B - F Reserved
00CB
Minor Fault Description 5
bit 0 E5 [MECHATROLINK Watchdog Timer Err]
bit 1 AEr [Station Address Setting Error]
bit 2 CyC [MECHATROLINK CommCycleSettingErr]
bit 3 HCA [High Current Alarm]
bit 4 LT-1 [Cooling Fan Maintenance Time]
bit 5 LT-2 [Capacitor Maintenance Time]
bit 6 - 7 Reserved
bit 8 EF1 [External Fault (Terminal S1)]
bit 9 EF2 [External Fault (Terminal S2)]
bit A SToF [Safe Torque OFF Hardware]
bit B STo [Safe Torque OFF]
bit C oL5 [Mechanical Weakening Detection 1]
bit D UL5 [Mechanical Weakening Detection 2]
bit E - F Reserved

Table of Contents