EasyManua.ls Logo

YASKAWA GA700 - Page 353

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
6
6.4 Faults
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 353
Code Name Causes Possible Solutions
There is increased motor loss from
overexcitation operation.
Lower the value set in n3-13
[OverexcitationBraking (OEB) Gain].
Set L3-04 4 [Stall Prevention during Decel
Overexcitation/High Flux].
Set n3-23 = 0 [Overexcitation Braking
Operation = Disabled].
The speed search-related parameters are
set incorrectly.
Examine the settings for all speed search related
parameters.
Adjust b3-03 [Speed Search Deceleration Time].
Set b3-24 = 1 [Speed Search Method Selection =
Speed Estimation] after Auto-Tuning.
Phase loss in the input power supply is
causing the output current to change.
Make sure that there is no phase loss, and repair
problems.
Note:
The drive detects this fault if the electronic thermal protector of the drive started the motor overload protection.
Do a Fault Reset to clear the fault.
L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.
Code Name Causes Possible Solutions
oL2 Drive Overload The load is too heavy. Decrease the load.
The acceleration/deceleration times or
cycle times are too short.
Examine the acceleration/deceleration times and
the motor start/stop frequencies (cycle times).
Increase the value set in C1-01 to C1-08
[Acceleration/Deceleration Times].
The V/f pattern does not fit the motor
qualities.
Examine the ratios between the V/f pattern
frequency and voltage. Lower the voltage if it is
too high compared to the frequency.
Adjust E1-04 to E1-10 [V/f Pattern Parameters].
Lower the values set in E1-08 [Mid Point A
Voltage] and E1-10 [Minimum Output Voltage]
For motor 2, adjust E3-04 to E3-10.
Note:
If E1-08 and E1-10 are set too low, the overload
tolerance is will decrease at low speeds.
The drive capacity is too small. Replace the drive with a larger capacity model.
Overload occurred while running at low
speed.
Decrease the load when running at low speed.
Replace the drive with a larger capacity model.
Decrease the value set in C6-02 [Carrier
Frequency Selection].
The torque compensation gain is too
large.
Decrease the value set in C4-01 [Torque
Compensation Gain] to make sure that the motor
does not stall.
The speed search-related parameters are
set incorrectly.
Examine the settings for all speed search related
parameters.
Adjust b3-03 [Speed Search Deceleration Time].
Set b3-24 = 1 [Speed Search Method Selection =
Speed Estimation] after Auto-Tuning.
Phase loss in the input power supply is
causing the output current to change.
Correct any wiring errors in the main circuit
drive input power.
Make sure that there is no phase loss, and repair
problems.
Note:
The drive detects this fault if the electronic thermal protector of the drive started the motor overload protection.
Do a Fault Reset to clear the fault.
L5-07 [Fault Reset Enable Select Grp1] disables the Auto Restart function.

Table of Contents

Other manuals for YASKAWA GA700

Related product manuals