EasyManua.ls Logo

YASKAWA GA700 - Page 365

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Troubleshooting
6
6.5 Minor Faults/Alarms
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 365
Code Name Causes Possible Solutions
External Fault [H1-01 = 2C to 2F] is
set to MFDI terminal S1, but the
terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF2 External Fault (Terminal
S2)
MFDI terminal S2 caused an external
fault through an external device.
1. Find the device that caused the external fault
and remove the cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal
S2.
External Fault [H1-02 = 2C to 2F] is
set to MFDI terminal S2, but the
terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF3 External Fault (Terminal
S3)
MFDI terminal S3 caused an external
fault through an external device.
1. Find the device that caused the external fault
and remove the cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal
S3.
External Fault [H1-03 = 2C to 2F] is
set to MFDI terminal S3, but the
terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF4 External Fault (Terminal
S4)
MFDI terminal S4 caused an external
fault through an external device.
1. Find the device that caused the external fault
and remove the cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal
S4.
External Fault [H1-04 = 2C to 2F] is
set to MFDI terminal S4, but the
terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF5 External Fault (Terminal
S5)
MFDI terminal S5 caused an external
fault through an external device.
1. Find the device that caused the external fault
and remove the cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal
S5.
External Fault [H1-05 = 2C to 2F] is
set to MFDI terminal S5, but the
terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal assigned to H2-01 to H2-03 = 10 [MFDO Function Select = Alarm] will be ON.
Code Name Causes Possible Solutions
EF6 External Fault (Terminal
S6)
MFDI terminal S6 caused an external
fault through an external device.
1. Find the device that caused the external fault
and remove the cause.
2. Clear the external fault input in the MFDI.
The wiring is incorrect. Correctly connect the signal line to MFDI terminal
S6.