Parameter List
10
10.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 641
No.
*1
Name Unit Default
-
Drive
Model
- 4168 4208 4250 4296
C6-01
Normal /
Heavy
Duty
Selection
-
HD1 ND1 HD1 ND1 HD1 ND1 HD1 ND1
0 1 0 1 0 1 0 1
o2-04
Drive
Model
(KVA)
Selection
Hex. A5 A6 A7 A8
E2-11
(E4-11)
Motor
Rated
Power
(kW)
kW 75 90 90 110 110 132 132 160
b3-04
V/f Gain
during
Speed
Search
% 60 60 60 60 60 60 60 60
b3-06
Speed
Estimation
Current
Level 1
- 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Speed
Estimation
ACR P
Gain
- 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8
b3-26
Direction
Determina
tion Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy
Saving
Filter Time
s 2.00 2.00 2.00 2.00 2.00 2.00 2.00 2.00
b8-04
Energy
Saving
Coefficient
Value
- 46.2 38.91 38.91 36.23 36.23 32.79 32.79 30.13
C5-17
(C5-37)
Motor
Inertia
kgm
2
0.90 1.10 1.10 1.90 1.90 2.10 2.10 3.30
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor
Rated
Current
(FLA)
A 130 156 156 190 190 223 223 270
E2-02
(E4-02)
Motor
Rated Slip
Hz 1.39 1.4 1.4 1.4 1.4 1.38 1.38 1.35
E2-03
(E4-03)
Motor No-
Load
Current
A 36 40 40 49 49 58 58 70
E2-05
(E4-05)
Motor
Line-to-
Line
Resistance
Ω 0.092 0.056 0.056 0.046 0.046 0.035 0.035 0.029
E2-06
(E4-06)
Motor
Leakage
Inductance
% 20 20 20 20 20 20 20 20
E2-10
(E4-10)
Motor Iron
Loss
W 1600 1760 1760 2150 2150 2350 2350 2850
E5-01
PM Motor
Code
Selection
- 1246 1246 1247 1247 1248 1248 1249 1249