11.2 A: Initialization Parameters
692 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
S-Curve Characteristics, Accel & Decel Time
Adjustment Parameter Name
C1-01, C1-03, C1-05, C1-07 Acceleration Time 1 to 4
C1-02, C1-04, C1-06, C1-08 Deceleration Time 1 to 4
C2-01 S-Curve Time @ Start of Accel
C2-02 S-Curve Time @ End of Accel
C2-03 S-Curve Time @ Start of Decel
C2-04 S-Curve Time @ End of Decel
Figure 11.5 S-curve Characteristics, Accel & Decel Time
Note:
When decreased operation times are necessary for the application, for example with cranes and hoists, do not use S-curve characteristic
times.
The default setting for C2-04 [S-Curve Time @ End of Decel] will be 0.00 seconds. The default setting for other S-curve characteristics
will be 0.20 seconds. Set the acceleration/deceleration times and S-curve characteristic time correctly for acceleration/deceleration start
up and end. The recommended setting of the S-curve characteristics time is 0.2 to 1.0 seconds.
When you use the C1-11 [Accel/Decel Time Switchover Freq], you can switch the acceleration/deceleration rate automatically during
acceleration/deceleration. The default setting is disabled.
When the Output Frequency C1-11, operate at the acceleration and deceleration times set in C1-01 and C1-02
When the Output Frequency < C1-11, operate at the acceleration and deceleration times set in C1-07 and C1-08
During low speed operation, if the Output Frequency < E1-09 [Minimum Output Frequency] in the S-Curve Time @ Start of Decel, the
drive will cancel the S-curve characteristics and will do DC Inject Braking at Stop (zero speed control).
Dwell Function at Start
Adjustment Parameter Name
b6-01 Dwell Reference at Start
b6-02 Dwell Time at Start
H2-xx = 5 Frequency Detection 2
Figure 11.6 Dwell Function at Start
Note:
If the mechanical operation of the holding brake is slow, use the Dwell Function at Start to prevent brake grinding (friction). Accelerate
after the brake is fully open.
When you use V/f Control and Open Loop Vector Control modes, set b6-01 [Dwell Reference at Start] > Frequency Detection 2
(brake open frequency).
If the motor torque is not sufficient during start up, use the DC Inject Braking function to secure the motor current (torque) before you
start the motor.
b2-02 [DC Injection Braking Current] recommended setting: 50% to 80% (V/f Control or Open Loop Vector Control)
b2-03 [DC Inject Braking Time at Start] recommended setting: 0.2 s to 0.5 s