11.2 A: Initialization Parameters
694 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Item Description
Sequence Circuit Configuration
Time chart: Increase Enter the analog signal as the torque compensation (torque bias) signal as specified by the load quantity
before drive operation until drive operation completes. The default setting is 10 V/100% torque.
Enter a positive polarity during a motoring load, and enter a negative polarity during a regenerative
load.
Time chart: Decrease Enter the analog signal as the torque compensation (torque bias) signal as specified by the load quantity
before drive operation until drive operation completes. The default setting is 10 V/100% torque.
Enter a negative polarity during a motoring load, and enter a positive polarity during a regenerative
load.
Note:
Holds through an external source to not change the torque compensation signal during run. If you change the torque compensation
signal during run, the motor can oscillate.
When you set motor reverse to the increase command and set motor forward to the decrease command, the polarity of the torque
compensation signal will reverse.
Analog Input FilterTime Constant
When b1-01 = 1 [Frequency Reference Selection 1 = Analog Input], it adds noise to the analog frequency
reference during run.
Minimize the effects of noise.