11.3 b: Application
712 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Figure 11.28 DC Current Level during DC Injection Braking at Start
Note:
If b2-08 < 100%, flux will develop very slowly.
When b2-08 = 0% the DC current level will be the DC Injection current set in b2-02 [DC Injection Braking Current].
If b2-08 is set too high, DC Injection Braking at start will make a loud audible noise. Adjust b2-08 to decrease the volume to the
permitted level.
b2-12: Short Circuit Brake Time @ Start
No.
(Hex.)
Name Description
Default
(Range)
b2-12
(01BA)
Short Circuit Brake
Time @ Start
Sets the Short Circuit Braking time at start.
0.00 s
(0.00 - 25.50 s)
This function restarts a stopped PM motor. The drive short circuits all three motor phases to make braking torque
in the motor.
Set this parameter to 0.00 to disable the function.
Note:
Short circuit Braking will let external forces rotate the PM motor. Use DC Injection Braking to prevent motor rotation from external
forces.
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
b2-13: Short Circuit Brake Time @ Stop
No.
(Hex.)
Name Description
Default
(Range)
b2-13
(01BB)
Short Circuit Brake
Time @ Stop
Sets the Short Circuit Braking time at stop.
A1-02 = 8: 0.00 s
Other than A1-02 =
8: 0.50 s
(0.00 - 25.50 s)
This function fully stops a PM motor with a large inertia during deceleration and will not let the inertia continue to
rotate the motor.
Short Circuit Braking operates for the time set in b2-13 when output frequency is less than the value set in b2-01
[DC Injection/Zero SpeedThreshold] or E1-09 [Minimum Output Frequency].
Set this parameter to 0.00 to disable the function.
Note:
Motor speed and load conditions can make it necessary to install a dynamic braking option on the drive.
b2-18: Short Circuit Braking Current
No.
(Hex.)
Name Description
Default
(Range)
b2-18
(0177)
Short Circuit Braking
Current
Sets the Short Circuit Braking Current as a percentage of the motor rated
current.
100.0%
(0.0 - 200.0%)
The Short Circuit Braking current cannot be higher than the drive rated current, although a higher current level
can be set using b2-18. The maximum rated current is 120% when the drive is set for Normal Duty (C6-01 = 1
[Normal Duty Rating]). The maximum rated current is 150% when the drive is set for Heavy Duty (C6-01 = 0
[Heavy Duty Rating]).
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV