Parameter Details
11
11.3 b: Application
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 743
■ b8-02: Energy Saving Gain
No.
(Hex.)
Name Description
Default
(Range)
b8-02
(01CD)
RUN
Expert
Energy Saving Gain
Sets the gain for Energy-saving control.
Determined by A1-02
(0.0 - 10.0)
Increase the setting value to increase energy saving. If the setting value is too large, the motor will stall.
■ b8-03: Energy Saving Filter Time
No.
(Hex.)
Name Description
Default
(Range)
b8-03
(01CE)
RUN
Expert
Energy Saving Filter
Time
Sets the responsiveness for Energy-saving control.
Determined by A1-
02, C6-01, and o2-04
(0.00 - 10.00 s)
Decrease the setting value to increase responsiveness. If the setting value is too low, operation will not be stable.
■ b8-04: Energy Saving Coefficient Value
No.
(Hex.)
Name Description
Default
(Range)
b8-04
(01CF)
Expert
Energy Saving
Coefficient Value
Sets the Energy-saving control coefficient to maintain maximum motor
efficiency. The default setting is for Yaskawa motors.
Determined by C6-
01, E2-11, o2-04
(0.00 - 655.00)
When you use a motor from a different manufacturer, increase the setting value in 5% increments to find the
minimum value for U1-08 [Output Power] at light loads.
When you decrease the setting value, it decreases the output voltage and decreases power consumption. If the
setting value is too low, the motor will stall.
Note:
When you do Rotational Auto-Tuning, the drive will automatically set the energy-saving coefficient.
■ b8-05: Power Detection Filter Time
No.
(Hex.)
Name Description
Default
(Range)
b8-05
(01D0)
Expert
Power Detection
Filter Time
Sets the time constant to measure output power.
20 ms
(0 - 2000 ms)
Decrease the setting value to increase responsiveness to load changes. If you set the value too low during
operation at light loads, motor speed is not stable.
■ b8-06: Search Operation Voltage Limit
No.
(Hex.)
Name Description
Default
(Range)
b8-06
(01D1)
Expert
Search Operation
Voltage Limit
Sets the voltage limit for Search Operation as a percentage where motor
rated voltage is a setting value of 100%.
0%
(0 - 100%)
The Search Operation changes the output voltage in small increments to find a setpoint at which the drive can use
minimum power to operate.
Set this parameter to 0 to disable Search Operation. This will not disable Energy-saving control.
If the setting value is too low, the motor will stall when loads suddenly increase.