760 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
C4-01: Torque Compensation Gain
No.
(Hex.)
Name Description
Default
(Range)
C4-01
(0215)
RUN
Torque
Compensation Gain
Sets the gain for the torque compensation function. Use this parameter value
for motor 1 when operating multiple motors.
Determined by A1-02
(0.00 - 2.50)
In V/f Control or CL-V/f Control, adjust the value in 0.05 unit increments for these conditions:
When torque is not sufficient during low-speed operation of 10 Hz or less, increase the setting value
When there is vibration in the motor or when the motor hunts when operating the drive with a light load,
decrease the setting value
When you use a long motor cable, increase the setting value.
Note:
Adjust C4-01 to make sure that the output current is not more than the drive rated current during low-speed operation.
In usual conditions, do not change this parameter in Open Loop Vector Control. It can have a negative effect on torque precision.
In usual conditions, do not change this parameter in PM Open Loop Vector Control. Setting this value too high can cause
overcompensation and motor oscillation.
C4-02: Torque Compensation Delay Time
No.
(Hex.)
Name Description
Default
(Range)
C4-02
(0216)
RUN
Torque
Compensation Delay
Time
Sets the torque compensation delay time. Usually it is not necessary to
change this setting.
Determined by A1-02
(0 - 60000 ms)
It can be necessary to adjust this parameter in these conditions:
If there is vibration in the motor, increase the setting.
If the motor speed or motor torque response is too slow, decrease the setting.
C4-03: Torque Compensation @ FWD Start
No.
(Hex.)
Name Description
Default
(Range)
C4-03
(0217)
Torque
Compensation @
FWD Start
Sets the amount of torque reference for forward start as a percentage of the
motor rated torque.
0.0%
(0.0 - 200.0%)
The drive uses the time constant set in C4-05 [Torque Compensation Time] to apply compensation.
When you start the motor with a forward Run command, enable this parameter. Set this parameter to 0.0 to disable
this function.
C4-04: Torque Compensation @ REV Start
No.
(Hex.)
Name Description
Default
(Range)
C4-04
(0218)
Torque
Compensation @
REV Start
Sets the amount of torque reference for reverse start as a percentage of the
motor rated torque.
0.0%
(-200.0 - 0.0%)
The drive uses the time constant set in C4-05 [Torque Compensation Time] to apply compensation.
When you start the motor with a reverse Run command, enable this parameter. Set this parameter to 0.0 to disable
this function.
C4-05: Torque Compensation Time
No.
(Hex.)
Name Description
Default
(Range)
C4-05
(0219)
Torque
Compensation Time
Sets the starting torque constant to use with C4-03 and C4-04 [Torque
Compensation @ FWD/REV Start].
10 ms
(0 - 200 ms)
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV