11.5 d: References
778 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change. Calculate the upper limit value with this formula:
Upper limit value = (E1-04) × (d2-01) / 100
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• To set d1-01 to 1-step speed parameter in a multi-step speed operation, set b1-01 = 0 [Frequency Reference Selection 1 = Keypad].
■ d1-02: Reference 2
No.
(Hex.)
Name Description
Default
(Range)
d1-02
(0281)
RUN
Reference 2
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• To set d1-02 to Multi-Step Speed 2, set H3-02, H3-06, and H3-10 ≠ 2 [MFAI Function Select ≠ Auxiliary Frequency Reference 1].
When the status is the default setting, set H3-06 = F [Terminal A3 Function Selection = Not Used].
■ d1-03: Reference 3
No.
(Hex.)
Name Description
Default
(Range)
d1-03
(0282)
RUN
Reference 3
Sets the frequency reference in the units from o1-03 [Keypad Display
Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• To set d1-03 to Multi-Step Speed 3, set H3-02, H3-06, and H3-10 ≠ 3 [MFAI Function Select ≠ Auxiliary Frequency Reference 2].
■ d1-04: Reference 4
No.
(Hex.)
Name Description
Default
(Range)
d1-04
(0283)
RUN
Reference 4
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = PM Advanced Open Loop Vector, PM Closed Loop Vector], the drive changes o1-03
= 1 [0.01% (100% = E1-04)].
• This parameter sets the frequency reference of Multi-Step Speed 4.
■ d1-05: Reference 5
No.
(Hex.)
Name Description
Default
(Range)
d1-05
(0284)
RUN
Reference 5
Sets the frequency reference in the units from o1-03 [Frequency Display
Unit Selection].
0.00 Hz
(0.00 - 590.00 Hz)