11.7 F: Options
824 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
F1-13: Encoder 1 Gear Teeth 2
No.
(Hex.)
Name Description
Default
(Range)
F1-13
(038C)
Encoder 1 Gear Teeth
2
Sets the number of gear teeth on the load side. This parameter and F1-12
[Encoder 1 Gear Teeth 1] set the gear ratio between the motor and encoder.
0
(0 - 1000)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-12 = 0 or F1-13 = 0, the gear ratio is 1.
F1-14: Encoder Open-Circuit Detect Time
No.
(Hex.)
Name Description
Default
(Range)
F1-14
(038D)
Encoder Open-
Circuit Detect Time
Sets the length of time that the drive must not receive a pulse signal to cause
a PGo [Encoder (PG) Feedback Loss].
2.0 s
(0.0 - 10.0 s)
If the drive does not detect output pulses from the encoder for longer than the time set in F1-14, the drive will
detect PGo.
Note:
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent] faults.
F1-18: Deviation 3 Detection Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-18
(03AD)
Deviation 3 Detection
Selection
Sets the number of rotations necessary to detect conditions that invert the
torque reference and rate of acceleration and cause dv3 [Inversion
Detection].
10
(0 - 10)
When the drive detects these two conditions at the same time for the number of times set in F1-18, the drive will
detect dv3.
The torque reference and acceleration are in opposite directions. For example, torque reference is in forward run
and the acceleration is in a negative direction.
The difference between the speed reference and the actual motor speed is more than 30%.
Note:
Reference the setting value for E5-11 [Encoder Z-Pulse Offset] and the δθ value found on the motor nameplate. A usual cause for a dv3
fault is an incorrect E5-11 setting.
Set F1-18 = 0 to disable the function.
F1-19: Deviation 4 Detection Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-19
(03AE)
Deviation 4 Detection
Selection
Sets the number of pulses necessary to cause dv4 [Inversion Prevention
Detection].
128
(0 - 5000)
The drive detects a dv4 [Inversion Prevention Detection] faultwhen the pulses in a reverse direction to the speed
reference are input for longer than the time set in F1-19.
Note:
Refer to the E5-11 [Encoder Z-Pulse Offset] value and the Δθ value shown on the motor nameplate. An incorrect E5-11 value will
frequently be the cause of a dv4 fault.
When you use the drive in an application that rotates the motor from the load side in the reverse direction of the speed reference, set
F1-19 = 0.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV