11.7 F: Options
826 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-33 = 0 or F1-34 = 0, the gear ratio is 1.
■ F1-34: Encoder 2 Gear Teeth 2
No.
(Hex.)
Name Description
Default
(Range)
F1-34
(03B3)
Encoder 2 Gear Teeth
2
Sets the number of gear teeth on the load side for motor 2. This parameter
and F1-33 [Encoder 2 Gear Teeth 1] set the gear ratio between the motor
and encoder.
0
(0 - 1000)
After you set the number of gear teeth, the drive uses this formula to calculate the motor speed:
Note:
When F1-33 = 0 or F1-34 = 0, the gear ratio is 1.
■ F1-35: Encoder 2 Pulse Monitor Scaling
No.
(Hex.)
Name Description
Default
(Range)
F1-35
(03BE)
Encoder 2 Pulse
Monitor Scaling
Sets the ratio between the pulse input and the pulse output of the encoder as
a 3-digit number for motor 2. The first digit is the numerator and the second
and third digits set the denominator.
001
(001 - 032, 102 - 132
(1 - 1/32))
When the setting value is a 3-digit value (xyz), the dividing ratio is (1 + x)/yz.
For example, when F1-35 = 032, the dividing ratio is 1/32.
Note:
For a single-pulse encoder, the dividing ratio for the monitor signal is 1:1.
■ F1-36: Encoder 2 PCB Disconnect Detect
No.
(Hex.)
Name Description
Default
(Range)
F1-36
(03B5)
Encoder 2 PCB
Disconnect Detect
Sets the function that enables and disables detection of a disconnected
encoder connection cable to cause PGoH [Encoder (PG) Hardware Fault]
for motor 2.
1
(0, 1)
0 : Disabled
1 : Enabled
■ F1-37: Encoder 2 Signal Selection
No.
(Hex.)
Name Description
Default
(Range)
F1-37
(03BD)
Encoder 2 Signal
Selection
Sets the number of channels for the signal to the encoder option card for
motor 2.
0
(0, 1)
0 : A Pulse Detection
1 : AB Pulse Detection