11.8 H: Terminal Functions
868 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ 2: External Reference 1/2 Selection
Setting Function Description
2 External Reference 1/
2 Selection
Sets the drive to use Run command source 1/2 or Reference command source 1/2 when in
REMOTE Mode.
Note:
When the drive is receiving a Run command, you cannot switch between reference sources.
ON : b1-15 = [Frequency Reference Selection 2], b1-16 [Run Command Selection 2]
OFF : b1-01 = [Frequency Reference Selection 1], b1-02 [Run Command Selection 1]
■ 3: Multi-Step Speed Reference 1
Setting Function Description
3 Multi-Step Speed
Reference 1
Uses speed references d1-01 to d1-08 [Multi-Step Speed Reference] to set a multi-step speed
reference.
Note:
Refer to “Setting Procedures for Multi-step Speed Operation” in “d: Reference Settings” for more information.
■ 4: Multi-Step Speed Reference 2
Setting Function Description
4 Multi-Step Speed
Reference 2
Uses speed references d1-01 to d1-08 [Multi-Step Speed Reference] to set a multi-step speed
reference.
Note:
Refer to “Setting Procedures for Multi-step Speed Operation” in “d: Reference Settings” for more information.
■ 5: Multi-Step Speed Reference 3
Setting Function Description
5 Multi-Step Speed
Reference 3
Uses speed references d1-01 to d1-08 [Multi-Step Speed Reference] to set a multi-step speed
reference.
Note:
Refer to “Setting Procedures for Multi-step Speed Operation” in “d: Reference Settings” for more information.
■ 6: Jog Reference Selection
Setting Function Description
6 Jog Reference
Selection
Sets the drive to use the JOG Frequency Reference (JOG command) set in d1-17. The JOG
Frequency Reference (JOG command) overrides Frequency References 1 to 16 (d1-01 to d1-16).
■ 7: Accel/Decel Time Selection 1
Setting Function Description
7 Accel/Decel Time
Selection 1
Sets the drive to use Acceleration/Deceleration Time 1 [C1-01, C1-02] or Acceleration/
Deceleration Time 2 [C1-03, C1-04].
Note:
Refer to “C1: Accel & Decel Time” for more information.
■ 8: Baseblock Command (N.O.)
Setting Function Description
8 Baseblock Command
(N.O.)
Sets the command that stops drive output and coasts the motor to stop when the input is ON.