EasyManua.ls Logo

YASKAWA GA700 - Page 873

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 873
Figure 11.83 JOG Operation Pattern
13: Reverse Jog
Setting Function Description
13 Reverse Jog
Sets the command to operate the motor in the reverse direction at the Jog Frequency set in d1-17
[Jog Reference].
Note:
It is not necessary to input the Run command.
The Reverse JOG command has priority over all other frequency references.
When the Forward JOG and Reverse JOG commands are activated at the same time for 500 ms or longer, the drive will ramp to stop.
14: Fault Reset
Setting Function Description
14 Fault Reset
Sets the command to reset the current fault when the Run command is inactive.
If the drive detects a fault, the drive will activate the fault relay output, turn off the output, and the motor will
coast to stop.
If the drive detects a fault for which you can set the stopping method, apply the appropriate Stopping Method.
Then push (RESET) on the keypad to turn the Run command OFF, or activate the fault reset terminal to reset
the fault.
Note:
The drive ignores the fault reset command when the Run command is active. Remove the Run command before trying to reset a fault.
15: Fast Stop (N.O.)
Setting Function Description
15 Fast Stop (N.O.)
Sets the command to ramp to stop in the deceleration time set in C1-09 [Fast Stop Time] when the
input terminal is ON while the drive is operating.
If you cancel the fast stop input, the drive will not restart the motor until you meet these conditions:
Fully stop the motor
Cancel the Run command
Cancel the fast stop command
Note:
To use the N.C. switch to input the fast stop command, set 17 (Fast Stop (N.C.)).
Refer to C1-09: Fast Stop Time for more information.
NOTICE: Fast deceleration can trigger an overvoltage fault. To prevent and uncontrolled motor and to make sure that the motor
stops quickly and safely, set an applicable Fast Stop time in C1-09 [Fast Stop Time]. When there is a fault, the drive output will
turn off and the motor will coast to stop.
16: Motor 2 Selection
Setting Function Description
16 Motor 2 Selection
Sets the command for the drive to operate motor 1 or motor 2. Stop the motors before switching.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents