EasyManua.ls Logo

YASKAWA GA700 - Page 875

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 875
Figure 11.84 Fast Stop Time Chart
18: Timer Function
Setting Function Description
18 Timer Function
Sets the command to start the timer function. Use this setting with Timer Output [H2-xx = 12].
Note:
Refer to b4: Timer Function for more information.
19: PID Disable
Setting Function Description
19 PID Disable
Sets the command to disable PID control when b5-01 = 1 to 8 [PID Mode Setting = Enabled].
ON : PID control disabled
OFF : PID control enabled
1A: Accel/Decel Time Selection 2
Setting Function Description
1A Accel/Decel Time
Selection 2
Set this function and H1-xx = 7[Accel/decel Time Selection 1] together. Sets the drive to use
Acceleration/Deceleration Time 3 [C1-05, C1-06] or Acceleration/Deceleration Time 4 [C1-07,
C1-08].
Note:
Refer to C1: Accel & Decel Time for more information.
1B: Programming Lockout
Setting Function Description
1B Programming
Lockout
Sets the command to prevent parameter changes when the terminal is OFF.
You can continue to view parameter setting values when the terminal is OFF [Parameters Cannot be Edited].
ON : Program Lockout
OFF : Parameter Write Prohibit
1E: Reference Sample Hold
Setting Function Description
1E Reference Sample
Hold
Sets the command to sample the frequency reference at terminals A1, A2, or A3 and hold the
frequency reference at that frequency.
When the terminal is active for 100 ms, this function reads a sample of the analog frequency reference and holds
that sample. When you input the sample/hold command again, the function again reads a sample of the analog
frequency reference and holds that sample. When you turn off the power, the drive erases the saved analog
frequency and resets the frequency reference to 0.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA700

Related product manuals