Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 883
Table 11.63 Up 2 Command, Down 2 Command
Func
tion
Frequency
Reference
Source
d4-03 d4-05 d4-01 Operation
Storing the Frequency Reference
or Frequency Bias
1
Multi-step speed
reference
0.00
0
0 When the Up 2 Command is active,
the drive accelerates the motor
(increases the bias value).
When the Down 2 Command is
active, the drive decelerates the
motor (decreases the bias value)
When the Up 2 Command and Down
2 Command are not active and when
the Up 2 Command and Down 2
Command are active, the drive holds
the output frequency (holds the bias
value).
When the frequency changes, it will
reset the bias.
For all other statuses, the drive will
follow the frequency reference.
Not stored.
2 1
When the bias value and frequency
reference are constant for 5 seconds
after the frequency reference hold
starts, the drive will add the bias value
to the enabled frequency reference,
then reset.
3 1 -
When the Up 2 Command is active,
the drive accelerates the motor.
When the Down 2 Command is
active, the drive decelerates the
motor.
For all other statuses, the drive will
follow the frequency reference.
Not stored.
4
Multi-step speed
reference
> 0 -
0 When the Up 2 Command is active,
the drive accelerates the motor to
Freq Reference + d4-03 (the bias
value will increase to the value set in
d4-03).
When the Down 2 Command is
active, the drive decelerates the
motor to Freq Reference - d4-03
(the bias value will decrease to the
value set in d4-03).
When the Up 2 Command and Down
2 Command are not active and when
the Up 2 Command and Down 2
Command are active, the drive holds
the output frequency (holds the bias
value).
When the frequency changes, it will
reset the bias.
For all other statuses, the drive will
follow the frequency reference.
Not stored.
5 1
When the bias value and frequency
reference are constant for 5 seconds
after the frequency reference hold
starts, the drive will add the bias value
to the enabled frequency reference,
then reset.
6
Others
(Analog input,
transmission)
0 0
0 When the Up 2 Command is active,
the drive accelerates the motor
(increases the bias value).
When the Down 2 Command is
active, the drive decelerates the
motor (decreases the bias value).
When the Up 2 Command and Down
2 Command are not active and when
the Up 2 Command and Down 2
Command are active, the drive holds
the output frequency (holds the bias
value).
During acceleration or deceleration,
when the frequency reference
increases or decreases more than d4-
07 [Analog Freq Ref Fluctuate
Limit], the drive holds the bias value
until the output frequency and the
actual frequency reference agree
(speed agreement).
Not stored.
7 1
When the bias value is constant for 5
seconds after the frequency reference
hold starts, the drive will store the bias
value in d4-06. You cannot rewrite the
frequency reference is not possible.
The drive will store only the bias
value.