11.8 H: Terminal Functions
892 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
H2-26: Comparator 2 Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-26
(1546)
Comparator 2
Monitor Selection
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx
[Monitor]. For example, set x-xx to 102 to monitor U1-02 [Output
Frequency].
103
(000 - 999)
Note:
The configurable monitor changes when the control method changes.
To use in through mode, set this parameter to 000 or 031. You can set the terminal output level from the PLC through MEMOBUS/
Modbus communications or the communication option.
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
H2-27: Comparator 2 Lower Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-27
(1547)
Comparator 2 Lower
Limit
Sets the lower limit detection level for comparator 1 when the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor
Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
H2-28: Comparator 2 Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-28
(1548)
Comparator 2 Upper
Limit
Sets the upper limit detection level for comparator 1 when the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor
Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
H2-29: Comparator 2 Hysteresis
No.
(Hex.)
Name Description
Default
(Range)
H2-29
(1549)
Comparator 2
Hysteresis
Sets the hysteresis level for comparator 2 when the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection] is the
100% value.
0.0%
(0.0 - 10.0%)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information
about the comparator function.
H2-30: Comparator 2 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-30
(154A)
Comparator 2 On-
Delay Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator 1 and Comparator 2] for more information
about the comparator function.
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents