11.8 H: Terminal Functions
892 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ H2-26: Comparator 2 Monitor Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-26
(1546)
Comparator 2
Monitor Selection
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx
[Monitor]. For example, set x-xx to 102 to monitor U1-02 [Output
Frequency].
103
(000 - 999)
Note:
• The configurable monitor changes when the control method changes.
• To use in through mode, set this parameter to 000 or 031. You can set the terminal output level from the PLC through MEMOBUS/
Modbus communications or the communication option.
• Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
■ H2-27: Comparator 2 Lower Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-27
(1547)
Comparator 2 Lower
Limit
Sets the lower limit detection level for comparator 1 when the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor
Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
■ H2-28: Comparator 2 Upper Limit
No.
(Hex.)
Name Description
Default
(Range)
H2-28
(1548)
Comparator 2 Upper
Limit
Sets the upper limit detection level for comparator 1 when the full scale
analog output for the monitor selected in H2-26 [Comparator 2 Monitor
Selection] is the 100% value.
0.0%
(0.0 - 300.0%)
Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
■ H2-29: Comparator 2 Hysteresis
No.
(Hex.)
Name Description
Default
(Range)
H2-29
(1549)
Comparator 2
Hysteresis
Sets the hysteresis level for comparator 2 when the full scale analog output
for the monitor selected in H2-26 [Comparator 2 Monitor Selection] is the
100% value.
0.0%
(0.0 - 10.0%)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator1 and Comparator 2] for more information
about the comparator function.
■ H2-30: Comparator 2 On-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-30
(154A)
Comparator 2 On-
Delay Time
Sets the on-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
Refer to H2-xx = 66 and 67 [Multi-Function Digital Out Function Select = Comparator 1 and Comparator 2] for more information
about the comparator function.