H2-31: Comparator 2 Off-Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-31
(154B)
Comparator 2 Off-
Delay Time
Sets the off-delay time for comparator 2.
0.0 s
(0.0 - 600.0 s)
Note:
Refer to H2-xx = 66 and 67 [MFDO Function Select = Comparator1 and Comparator2] for more information about the comparator
function.
H2-32: Comparator 1 Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H2-32
(159A)
Comparator 1 Filter
Time
Sets the time constant that is applied to the primary delay filter used for the
analog output of the monitor selected with H2-20 [Comparator 1 Monitor
Selection].
0.0s
(0.0 - 10.0 s)
H2-33: Comparator1 Protection Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-33
(159B)
Comparator1
Protection Selection
Sets drive operation when it detects CP1 [Comparator1 Limit Fault].
4
(0 - 4)
0 : Ramp to Stop
The drive ramps to stop in the set deceleration time. Fault relay output terminal MA-MC activates and terminal
MB-MC deactivates.
1 : Coast to Stop
The drive output shuts off and the motor coasts to stop. Fault relay output terminal MA-MC activates and terminal
MB-MC deactivates.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-
MC activates and terminal MB-MC deactivates.
3 : Alarm Only
The keypad shows CP1 and the drive continues operation at the current frequency reference.
Note:
The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.
4 : Digital Output Only
H2-34: Comparator 2 Filter Time
No.
(Hex.)
Name Description
Default
(Range)
H2-34
(159C)
Comparator 2 Filter
Time
Sets the time constant that is applied to the primary delay filter used for the
analog output of the monitor selected with H2-26 [Comparator 2 Monitor
Selection].
0.0s
(0.0 - 10.0 s)
H2-35: Comparator2 Protection Selection
No.
(Hex.)
Name Description
Default
(Range)
H2-35
(159D)
Comparator2
Protection Selection
Sets drive operation when it detects CP2 [Comparator2 Limit Fault].
4
(0 - 4)
0 : Ramp to Stop
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV