11.8 H: Terminal Functions
920 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
■ 7: Torque Detection Level
Setting Function Description
7 Torque Detection
Level
Enters a signal to adjust the overtorque/undertorque detection level.
When A1-02 = 0, 1, 5 [Control Method Selection = V/f Control, Closed Loop V/f Control, PM Open Loop Vector
Control], the drive rated current is 100%. When A1-02 = 2, 3, 4, 6, 7, 8 [Open Loop Vector Control, Closed Loop
Vector Control, Advanced OpenLoop Vector Control, PM Advanced Open Loop Vector, PM Closed Loop Vector
Control, or EZ Open Loop Vector Control], the motor rated current is 100%.
Note:
Use this function with L6-01 [Torque Detection Selection 1]. This parameter functions as an alternative to L6-02 [Torque Detection
Level 1].
■ 8: Stall Prevent Level During Run
Setting
Value
Function Description
8 Stall Prevent Level
During Run
Enters a signal to adjust the stall prevention level during run if the drive rated current is 100%.
Note:
The correct stall prevention level during run is the lower value between:
• The analog input value for the MFAI terminal, or
• The value of L3-06 [Stall Prevent Level during Run].
Figure 11.111 Stall Prevention Level during Run through Analog Input
■ 9: Output Frequency Lower Limit
Setting Function Description
9 Output Frequency
Lower Limit
Enters a signal to adjust the output frequency lower limit level if E1-04 [Maximum Output
Frequency] = 100%.
■ B: PID Feedback
Setting Function Description
B PID Feedback
Enters the PID feedback value.
Sets the current PID feedback value when the 10 V (or 20 mA) analog signal is input as 100%.
When you use this function, set b5-01 = 1 to 8 [PID Function Setting = Enabled].
■ C: PID Setpoint
Setting Function Description
C PID Setpoint
Enters the PID setpoint.
Sets the current PID setpoint value when the 10 V (or 20 mA) analog signal is input as 100%.
Set b5-01 = 1 to 8 [PID Mode Setting = Enabled] when using this function.