11.8 H: Terminal Functions
926 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Note:
• The configurable monitor changes when the control method changes.
• To use in through mode, set this parameter to 000 or 031. You can set the terminal AM output level from the PLC through
MEMOBUS/Modbus communications or the communication option.
■ H4-05: Terminal AM Analog Output Gain
No.
(Hex.)
Name Description
Default
(Range)
H4-05
(0421)
RUN
Terminal AM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
50.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-08 [Terminal AM Signal Level Select].
Examples of possible settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
• H4-04 = 103 [Terminal AM Analog Output Select = Output Current]
• H4-05 = 50.0%
• H4-06 = 0.0% [Terminal AM Analog Output Bias = 0.0%]
• H4-08 = 0 [0 to 10 V]
■ H4-06: Terminal AM Analog Output Bias
No.
(Hex.)
Name Description
Default
(Range)
H4-06
(0422)
RUN
Terminal AM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-08 [Terminal AM Signal Level Select].
■ H4-07: Terminal FM Signal Level Select
No.
(Hex.)
Name Description
Default
(Range)
H4-07
(0423)
Terminal FM Signal
Level Select
Sets the MFAO terminal FM output signal level.
0
(0 - 2)
Note:
Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.
0 : 0-10 VDC
1 : -10 +10 VDC
2 : 4-20 mA
■ H4-08: Terminal AM Signal Level Select
No.
(Hex.)
Name Description
Default
(Range)
H4-08
(0424)
Terminal AM Signal
Level Select
Sets the MFAO terminal AM output signal level.
0
(0 - 2)
Note:
Set jumper S5 on the terminal board to the correct position after changing this parameter.
0 : 0-10 VDC
1 : -10 +10 VDC
2 : 4-20 mA