11.8 H: Terminal Functions
926 YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual
Note:
The configurable monitor changes when the control method changes.
To use in through mode, set this parameter to 000 or 031. You can set the terminal AM output level from the PLC through
MEMOBUS/Modbus communications or the communication option.
H4-05: Terminal AM Analog Output Gain
No.
(Hex.)
Name Description
Default
(Range)
H4-05
(0421)
RUN
Terminal AM Analog
Output Gain
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
50.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-08 [Terminal AM Signal Level Select].
Examples of possible settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
H4-04 = 103 [Terminal AM Analog Output Select = Output Current]
H4-05 = 50.0%
H4-06 = 0.0% [Terminal AM Analog Output Bias = 0.0%]
H4-08 = 0 [0 to 10 V]
H4-06: Terminal AM Analog Output Bias
No.
(Hex.)
Name Description
Default
(Range)
H4-06
(0422)
RUN
Terminal AM Analog
Output Bias
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
0.0%
(-999.9 - +999.9%)
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with
H4-08 [Terminal AM Signal Level Select].
H4-07: Terminal FM Signal Level Select
No.
(Hex.)
Name Description
Default
(Range)
H4-07
(0423)
Terminal FM Signal
Level Select
Sets the MFAO terminal FM output signal level.
0
(0 - 2)
Note:
Set jumper S5 on the control circuit terminal block accordingly when changing these parameters.
0 : 0-10 VDC
1 : -10 +10 VDC
2 : 4-20 mA
H4-08: Terminal AM Signal Level Select
No.
(Hex.)
Name Description
Default
(Range)
H4-08
(0424)
Terminal AM Signal
Level Select
Sets the MFAO terminal AM output signal level.
0
(0 - 2)
Note:
Set jumper S5 on the terminal board to the correct position after changing this parameter.
0 : 0-10 VDC
1 : -10 +10 VDC
2 : 4-20 mA
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents

Other manuals for YASKAWA GA700

Related product manuals