EasyManua.ls Logo

YASKAWA GA700 - Page 929

YASKAWA GA700
1053 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Details
11
11.8 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710617 05F YASKAWA AC Drive GA700 Technical Manual 929
Figure 11.116 Drive Transmit Wait Time
H5-09: CE Detection Time
No.
(Hex.)
Name Description
Default
(Range)
H5-09
(0435)
CE Detection Time
Sets the detection time for CE [Modbus Communication Error] issues when
communication stops.
2.0 s
(0.0 - 10.0 s)
H5-10: Modbus Register 0025H Unit Sel
No.
(Hex.)
Name Description
Default
(Range)
H5-10
(0436)
Modbus Register
0025H Unit Sel
Sets the unit of measure used for the MEMOBUS/Modbus communications
monitor register 0025H (output voltage reference monitor).
0
(0, 1)
0 : 0.1 V units
1 : 1 V units
H5-11: Comm ENTER Command Mode
No.
(Hex.)
Name Description
Default
(Range)
H5-11
(043C)
Comm ENTER
Command Mode
Sets the function to make the Enter command necessary to change
parameters through MEMOBUS/Modbus communications.
0
(0, 1)
0 : ENTER Command Required
You must use the Enter command to enable changes to parameters. Make all parameter changes then input the
Enter command.
1 : ENTER Command Not Required
It is not necessary to input the Enter command to change parameters.
H5-12: Run Command Method Selection
No.
(Hex.)
Name Description
Default
(Range)
H5-12
(043D)
Run Command
Method Selection
Sets the input method for the Run command when b1-02 = 2 [Run
Command Selection 1 = Memobus/Modbus Communications] or b1-16 = 2
[Run Command Selection 2 = Memobus/Modbus Communications].
0
(0, 1)
0 : FWD/Stop, REV/Stop
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor forward Run command (bit
0 = 1) and the stop command (bit 0 = 0). The drive uses bit 1 in the motor reverse Run command (bit 1 = 1) and
the stop command (bit 1 = 0).
1 : Run/Stop, FWD/REV
The drive uses bit 0 in command data 0001H of the MEMOBUS register in the motor Run command (bit 0 = 1)
and the stop command (bit 0 = 0). The drive uses bit 1 in the direction of motor rotation command (Forward run
(bit1 = 0) or Reverse run (bit 1 = 1)).
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV

Table of Contents