Section 7.  Installation 
 
 
•  Execute conditional code 
•  Use multiple sequential scans, each with a scan count 
 
 
 Groundwater Pump Test 
'This program example demonstrates the use of multiple scans in a program by running a 
'groundwater pump test.  Note that Scan() time units of Sec have been changed to mSec for  
'this demonstration to allow the program to run its course in a short time.  To use this  
'program for an actual pump test, change the Scan() instruction mSec arguments to Sec. You 
'will also need to put a level measurement in the MeasureLevel subroutine. 
 
'A groundwater pump test requires that water level be measured and recorded 
'according to the following schedule: 
 
'Minutes into Test       Data-Output Interval 
'----------------- -------------------- 
'      0-10                   10 seconds 
'     10-30                   30 seconds 
'    30-100                   60 seconds 
'   100-300                  120 seconds 
'  300-1000                  300 seconds 
'      1000+                 600 seconds 
'Declare Variables 
Public PTemp 
Public Batt_Volt 
Public Level 
Public LevelMeasureCount As Long 
Public ScanCounter(6) As Long 
 
'Declare Data Table 
DataTable(LogTable,1,-1) 
 Minimum(1,Batt_Volt,FP2,0,False) 
 Sample(1,PTemp,FP2) 
 Sample(1,Level,FP2) 
EndTable 
 
'Declare Level Measurement Subroutine 
Sub MeasureLevel 
 LevelMeasureCount = LevelMeasureCount + 1 'Included to show passes through sub-routine 
 'Level measurement instructions goes here 
EndSub 
'Main Program 
BeginProg 
 
 'Minute 0 to 10 of test: 10-second data-output interval 
 Scan(10,mSec,0,60) 'There are 60 10-second scans in 10 minutes 
 ScanCounter(1) = ScanCounter(1) + 1 'Included to show passes through this scan 
 Battery(Batt_volt) 
 PanelTemp(PTemp,250) 
 Call MeasureLevel 
 
 'Call Output Tables 
 CallTable LogTable 
 NextScan