Section 8.  Operation 
 
 
Operating systems can also be sent using the program Send feature in datalogger 
support software
 (p. 86). A full reset does not occur in this case.    Beginning with 
CR800 operating system v.16, settings and fields in the Status table are preserved 
when sending a subsequent operating system by this method; data tables are 
erased.    Rely on this feature only with an abundance of caution when sending an 
OS to CR800s in remote, expensive to get to, or difficult-to-access locations. 
 
8.8.3.2  Program Send Reset 
Final-storage (p. 499) data are erased when user programs are uploaded, unless 
preserve / erase data options are used.    Preserve / erase data options are presented 
when sending programs using File Control Send
 (p. 498) command and CRBasic 
Editor Compile, Save and Send
 (p. 494). See Preserving Data at Program Send (p. 
170) 
for a more-detailed discussion of preserve / erase data at program send. 
 
8.8.3.3  Manual Data-Table Reset 
Data-table memory is selectively reset from 
•  Support software Station Status
 (p. 516) command 
•  CR1000KD Keyboard/Display: Data | Reset Data Tables 
 
8.8.3.4  Formatting Drives 
CPU:, USR:, andUSB: drives can be formatted individually.    Formatting a drive 
erases all files on that drive.    If the currently running user program is found on 
the drive to be formatted, the program will cease running and any SRAM data 
associated with the program are erased.    Drive formatting is performed through 
datalogger support software
 Format (p. 498) command. 
 
8.8.4  File Management in CR800 Memory 
As summarized in table File Control Functions (p. 416), files in CR800 memory 
(program, data, CAL, image) can be managed or controlled with datalogger 
support software
 (p. 86), the CR1000KD keyboard/display (see Keyboard Display 
— Details 
(p. 443)), Web API (p. 435, p. 435), or CoraScript (p. 493). Use of CoraScript is 
described in the LoggerNet software manual, which is available at 
www.campbellsci.com.    More information on file attributes that enhance 
datalogger security, see the Security — Overview
 (p. 84) section.