Appendix A. Info Tables and Settings 
 
 
 Info Tables and Settings: D 
 
 
 
Keyword  Data Type 
• Where to Find 
 
Description 
 
 
 
DataFillDays() 
Numeric  Y 
•  DataTableInfo table 
Reports the time required to fill a data table.    Each table has its own entry. 
 
 
 
DataRecord 
Size() 
Numeric  Y 
•  DataTableInfo table 
Reports the number of records in a data table. 
 
 
 
DataTable 
Name() 
String  Y 
•  DataTableInfo table 
Reports the names of data tables. Array elements are in the order the data tables are 
declared in the CRBasic program. 
 
 
 
DNS() 
String   
•  Settings Editor: Ethernet, CS I/O IP, PPP, Wi-Fi | DNS Server 1, DNS Server 2 
•  Keyboard: Settings (Network Services) 
Specifies the addresses of two domain name servers that the CR800 can use to resolve 
domain names to IP addresses. Note that if DHCP is used to resolve IP information, the 
addresses obtained via DHCP are appended to this list. Defaults to 0.0.0.0. Form: 0–255.0–
255.0–255.0-255 
 
 
 
     
 
 
 
 Info Tables and Settings: E 
 
 
 
Keyword  Data Type 
• Where to Find 
 
Description 
 
 
 
ErrorCalib 
Numeric  Y 
•  Status table field: ≈25 
Number of erroneous calibration values measured. Erroneous values are discarded. Auto 
self-calibration runs in a hidden slow-sequence scan. Updated at startup or auto self-
calibration. 
 
 
 
EthernetEnable 
Numeric   
•  Settings Editor: Ethernet | Ethernet Enable 
 
 
 
EthernetInfo 
String   
•  Settings Editor: Ethernet | {info box} 
 
 
 
EthernetPower 
UINT2   
•  Settings Editor: Ethernet | Ethernet Power 
0 to 4, 4 = always off