Section 7.  Installation 
 
 
 SlowSequence 
 
 Do 
 SDI12SensorSetup(10,1,0,1) 
 Delay(1,500,mSec) 
 SDI12SensorResponse(SDI_Source) 
 Loop 
 
 EndSequence 
 
 
 
 SDI-12 Sensor Configuration CRBasic Example — Results 
Measurement 
Command from 
SDI-12 Recorder 
Source Variables 
Accessed from the 
CR800 acting as a 
SDI-12 Sensor 
Contents of 
Source Variables 
0M! 
Source(1), Source(2) 
Temperature °C, battery 
voltage 
0M0! 
Same as 0M!   
0M1! 
Source(3), Source(4) 
Temperature °F, battery 
voltage 
0M2! 
Source(5), Source(6) 
Temperature °C, battery 
mV 
0M3! 
Source(7), Source(8) 
Temperature °F, battery 
mV 
0M4! 
Source(9), Source(10) 
Serial number, lithium 
battery voltage 
 
 
7.7.14.4 SDI-12 Power Considerations 
When a command is sent by the CR800 to an SDI-12 probe, all probes on the 
same SDI-12 port will wake up. However, only the probe addressed by the 
datalogger will respond.    All other probes will remain active until the timeout 
period expires. 
Example: 
Probe: Water Content 
Power Usage: 
•  Quiescent: 0.25 mA 
•  Measurement: 120 mA 
•  Measurement time: 15 s