Section 8.  Operation 
 
 
Methods of enabling pass-code lockout security include the following: 
•  Settings – Security(1) 
(p. 549), Security(2) and Security(3) registers are 
writable variables in the Status table wherein the pass codes for security 
levels 1 through 3 are written, respectively. 
•  CR1000KD Keyboard/Display settings 
•  Device Configuration Utility (DevConfig) – Security passwords 1 
through 3 are set on the Deployment tab. 
•  SetSecurity() instruction – SetSecurity() is only executed at program 
compile time.    It may be placed between the BeginProg and Scan() 
instructions. 
Note Deleting SetSecurity() from a CRBasic program is not equivalent 
to SetSecurity(0,0,0).    Settings persist when a new program is 
downloaded that has no SetSecurity() instruction. 
Level 1 must be set before Level 2.  Level 2 must be set before Level 3. If a level 
is set to 0, any level greater than it will be set to 0.    For example, if level 2 is 0 
then level 3 is automatically set to 0.    Levels are unlocked in reverse order: level 
3 before level 2, level 2 before level 1.    When a level is unlocked, any level 
greater than it will also be unlocked, so unlocking level 1 (entering the Level 1 
security code) also unlocks levels 2 and 3. 
Functions affected by each level of security are: 
•  Level 1 — Collecting data, setting the clock, and setting variables in the 
Public table are unrestricted, requiring no security code.    If Security1 
code is entered, read/write values in the Status table can be changed, and 
the datalogger program can be changed or retrieved. 
•  Level 2 — Data collection is unrestricted, requiring no security code. If 
the user enters the Security2 code, the datalogger clock can be changed 
and variables in the Public table can be changed. 
•  Level 3 — When this level is set, all communication with the datalogger 
is prohibited if no security code is entered.    If Security3 code is entered, 
data can be viewed and collected from the datalogger (except data 
suppressed by the TableHide() instruction in the CRBasic program). If 
Security2 code is entered, data can be collected, public variables can be 
set, and the clock can be set.    If Security1 code is entered, all functions 
are unrestricted. 
 
8.7.2.1  Pass-Code Lockout By-Pass 
Pass-code lockouts can be bypassed at the datalogger using a CR1000KD 
Keyboard/Displaykeyboard display. Pressing and holding the Del key while 
powering up a CR800 will cause it to abort loading a program and provide a 120 
second window to begin changing or disabling security codes in the settings editor 
(not Status table) with the keyboard display.