5.1 Registering Loggers in Logger Utility
72
Connecting one PC to multiple instrument's in a HUB.
Use a straight cable to connect the PC to the HUB and to connect the instrument
to the HUB.
When building a local network with no outside connections, it is recommended
that private IP addresses be used for the IP addresses.
Make the same settings on the PC as shown left. Set the IP address manually.
Set the instrument as shown below, so that every instrument has a unique host
name and IP address.
* If you set an IP address, it does not matter if a host name is not entered.
The first instrument (The settings are made manually)
Setting Items Settings
Host Name
LOGGER1
*
IP Address 192.168.1.2
The second instrument (The settings are made manually)
Setting Items Settings
Host Name
LOGGER2
*
IP Address 192.168.1.3
The third instrument (The settings are made manually)
Setting Items Settings
Host Name
LOGGER3
*
IP Address 192.168.1.4
Common settings
Setting Items Settings
DHCP OFF
Subnet Mask 255.255.255.0
Gateway OFF
Port Number 880X