PTP - Precision Time Protocol
357
4.14.8 ptp sync-lower-bound
Configure the lower bound for the PTP clock synchronization
(unit: nanoseconds, min.: 0, max.: 999999999 (10
9
-1), default: 30).
Note: the lower bound always has to be smaller than the upper bound.
Format
ptp sync-lower-bound <0-999999999>
Mode
Global Config
4.14.9 ptp sync-upper-bound
Configure the upper bound for the PTP clock synchronization
(unit: nanoseconds, min.: 31, max.: 1000000000 (10
9
), default: 5000).
Note: the upper bound always has to be larger than the lower bound.
Format
ptp sync-upper-bound <31-1000000000>
Mode
Global Config