NOTE: After a PSM is powered on, it can take up to 60 seconds for status indicators—such
as the status LEDs on the PSM and the show chassis command display—to indicate that
the PSM is functioning normally. Ignore error indicators that appear during the first 60
seconds.
If any of the status LEDs indicates that the PSM is not functioning normally, repeat the installation and
cabling procedures.
11. Verify that the INP0 or INP1 LEDs on the PSM are lit green steadily if using two feeds.
NOTE: The DIP switches 0 and 1 must be set to the ON position for a two feed installation.
12. On the external management device connected to the Control Board and Routing Engine (CB-RE),
monitor the startup process to verify that the system has booted properly.
NOTE: If the system is completely powered off when you power on the PSM, the Routing
Engine boots as the PSM completes its startup sequence. Normally, the router boots from
the Junos OS on the CompactFlash card.
To power off the system after the Routing Engine finishes booting, see Powering Off the
DC-Powered MX2020 Router.
13. Verify the MX2020 router power up, system initialization, and status, see “Initially Configuring the
MX2020 Router” on page 347.
RELATED DOCUMENTATION
Preventing Electrostatic Discharge Damage to an MX2020 Router
Replacing an MX2000 DC Power Supply Module (240 V China) | 408
Replacing an MX2000 DC Power Distribution Module (240 V China) | 396
330

Table of Contents

Other manuals for Juniper MX2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper MX2020 and is the answer not in the manual?

Juniper MX2020 Specifications

General IconGeneral
BrandJuniper
ModelMX2020
CategoryNetwork Router
LanguageEnglish

Related product manuals