Figure 170: Installing a Three-Phase Delta AC Power Distribution Module (MX2008)
9. Remove the cover of the metal AC wiring compartment.
10. Unscrew the retaining nut from the AC power cord.
11. Place the retaining nut inside the metal wiring compartment.
12. Insert the wires of the AC power cord through the hole of the retaining nut and rubber grommet.
13. Insert the wires of the AC power cord through the hole of the metal wiring compartment.
14. Connect the wires to the AC terminal block on the three-phase delta AC PDM (see
Figure 171 on page 369). Loosen each of the input terminals or grounding point screws, and insert the
wire into the grounding point or input terminal, and tighten the screw (see Table 99 on page 370 for
approved AC wire gauge).
To insert wires into the terminal block that serves six PSMs:
a. Insert the grounding wire into the grounding point labeled GND.
b. Insert the wire labeled L1 into the input terminal labeled A1.
c. Insert the wire labeled L2 into the input terminal labeled B1.
d. Insert the wire labeled L3 into the input terminal labeled C1.
368

Table of Contents

Other manuals for Juniper MX2020

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Juniper MX2020 and is the answer not in the manual?

Juniper MX2020 Specifications

General IconGeneral
BrandJuniper
ModelMX2020
CategoryNetwork Router
LanguageEnglish

Related product manuals