Parameter Reference D-57
AC30V series Variable Speed Drive
PNO Parameter Descriptions
0039 Anin 01 Value
Terminal X11.1
The value returned by the signal processing electronics. For unipolar ranges, (all except -10..10V), the value is expressed as a
percentage of the hardware range. For the -10..10V range the full range signal is expressed as -100% to +100%.
0040 Anin 01 Break
When the input range is set to 4..20mA a break is defined as an input signal less than 3mA. Otherwise this parameter is set to
FALSE.
0041 Anin 02 Value
Terminal X11.2
The value returned by the signal processing electronics. For the 0..10V range the value is expressed as a percentage of the
hardware range, (0 to 100%). For the -10..10V range the full range signal is expressed as -100% to +100%.
0042 Anout 01 Value
Terminal X11.3
The desired output value expressed as a percentage of the output range.
Range
Mapping
0..10V
0% gives 0V, 100% gives 10V
0..20MA
0% gives 0mA, 100% gives 20mA
4..20MA
0% gives 4mA, 100% gives 20mA
0043 Anout 02 Value
Terminal X11.4
The desired output value expressed as a percentage of the output range.
Range
Mapping
-10..10V
-100% gives -10V, 100% gives 10V
0..10V
0% gives 0V, 100% gives 10V
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals