EasyManuals Logo

Parker AC30 series User Manual

Parker AC30 series
453 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #410 background imageLoading...
Page #410 background image
D-138 Parameter Reference
AC30V series Variable Speed Drive
PNO
Name
Path(s)
Type
Default
Range
Units
WQ
View
Notes
MBus
0611
App Control Word.SWITCH ON
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01749
0612
App Control Word.ENABLE VOLTAGE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01751
0613
App Control Word.NOT QUICKSTOP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01753
0614
App Control Word.ENABLE OPERATION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01755
0618
App Control Word.RESET FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01763
0619
App Control Word.EXTERNAL FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01765
0623
App Control Word.USE JOG REFERENCE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01773
0624
App Control Word.REVERSE DIRECTION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01775
0625
App Control Word.AUTO INITIALISE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01777
0626
App Control Word.EVENT TRIGGERED OP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
ENGINEER
2
01779
0627
Comms Control Word Parameters::Motor Control::Sequencing
WORD
(bitfield)
0000
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
10:USE COMMS CONTROL
11:USE COMMS
REFERENCE
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
ALWAYS TECHNICIAN 2
01781
0628
Comms Control Word.SWITCH ON
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01783
0629
Comms Control Word.ENABLE VOLTAGE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01785
0630
Comms Control Word.NOT QUICKSTOP
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01787
0631
Comms Control Word.ENABLE OPERATION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01789
0635
Comms Control Word.RESET FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01797
0636
Comms Control Word.EXTERNAL FAULT
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01799
0638
Comms Control Word.USE COMMS
CONTROL
Parameters::Motor Control::Sequencing BOOL FALSE ALWAYS TECHNICIAN 2
01803
0639
Comms Control Word.USE COMMS
REFERENCE
Parameters::Motor Control::Sequencing BOOL FALSE ALWAYS TECHNICIAN 2
01805
0640
Comms Control Word.USE JOG
REFERENCE
Parameters::Motor Control::Sequencing BOOL FALSE ALWAYS TECHNICIAN 2
01807
0641
Comms Control Word.REVERSE DIRECTION
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01809
0642
Comms Control Word.AUTO INITIALISE
Parameters::Motor Control::Sequencing
BOOL
FALSE
ALWAYS
TECHNICIAN
2
01811
0643
Comms Control Word.EVENT TRIGGERED
OP
Parameters::Motor Control::Sequencing BOOL FALSE ALWAYS TECHNICIAN 2
01813
0644
Control Word Parameters::Motor Control::Sequencing
WORD
(bitfield)
0:SWITCH ON
1:ENABLE VOLTAGE
2:NOT QUICKSTOP
3:ENABLE OPERATION
7:RESET FAULT
8:EXTERNAL FAULT
10:USE COMMS CONTROL
11:USE COMMS
REFERENCE
12:USE JOG REFERENCE
13:REVERSE DIRECTION
14:AUTO INITIALISE
15:EVENT TRIGGERED OP
NEVER TECHNICIAN
01815
0645
Control Word.SWITCH ON
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01817
0646
Control Word.ENABLE VOLTAGE
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01819
0647
Control Word.NOT QUICKSTOP
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01821
0648
Control Word.ENABLE OPERATION
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01823
0652
Control Word.RESET FAULT
Parameters::Motor Control::Sequencing
BOOL
NEVER
TECHNICIAN
01831
www.comoso.com

Table of Contents

Other manuals for Parker AC30 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker AC30 series and is the answer not in the manual?

Parker AC30 series Specifications

General IconGeneral
Control ModesClosed-loop vector
FeedbackEncoder
Operating Temperature0 to 40°C (32 to 104°F) standard, -20 to 50°C (-4 to 122°F) with derating
ProtectionOvercurrent, Overvoltage, Undervoltage
CommunicationRS485

Related product manuals