EasyManua.ls Logo

Rockwell Automation Allen-Bradley Kinetix 5700 - Remove;Install the Ground Screw;Jumper

Rockwell Automation Allen-Bradley Kinetix 5700
456 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
130 Rockwell Automation Publication 2198-UM002L-EN-P - October 2021
Chapter 5 Connect the Kinetix 5700 Drive System
Remove/Install the Ground
Screw/Jumper
We recommend that you remove or install the ground screw/jumper when the
drive module is removed from the panel and placed on its side on a solid work
surface (does not apply to catalog numbers 2198-RPxxx, 2198-S263-ERSx, or
2198-S312-ERSx).
To access or remove/install the ground screw on DC-bus power supplies, dual-
axis inverters, and the iTRAK power supply, open the small plastic door on the
right side of the module.
Figure 80 - Remove/Install the Ground Screw
Single-axis inverters (catalog numbers 2198-S086-ERSx, 2198-S130-ERSx, and
2198-S160-ERSx) have a ground-jumper access door on the back of the unit.
Two captive screws secure the jumper.
Figure 81 - Remove/Install the Single-axis Inverter Ground Jumper
IMPORTANT
To determine if you need to remove or install the ground screw/jumper,
see Ground Screw/Jumper Settings on page 127.
ATTENTION: When the ground screw/jumper is not installed on DC-bus
power supplies, the risk of equipment damage exists because the unit no
longer maintains line-to-neutral or line-to-line voltage protection.
Ground Screw
Access Door
DC-bus Power Supply,
Dual-axis Inverter, or iTRAK Power Supply (side view)
(DC-bus power supply is shown)
Ground Screw
To determine if you need to remove or
install the ground screw, see
Ground Screw/Jumper Settings
on page 127
.
ATTENTION: To avoid personal injury, the ground screw/jumper access
door must be kept closed when power is applied. If power was present and
then removed, wait at least 5 minutes for the DC-bus voltage to dissipate
and verify that no DC-bus voltage exists before accessing the ground
screw/ jumper. This applies to the DC-bus power supply, regenerative bus
supply, dual-axis inverters, and single-axis inverters.
Ground Jumper
Access Door
2198-S086-ERSx, 2198-S130-ERSx, and 2198-S160-ERSx
Single-axis Inverter
(rear view)
Captive Screws (2)
Jumper
TIP
Hold the jumper with
needle-nose pliers and
remove/install the
captive screws.
To determine if you need to remove or
install the ground jumper, see
Ground Screw/Jumper Settings
on page 127
.

Table of Contents

Other manuals for Rockwell Automation Allen-Bradley Kinetix 5700

Related product manuals