Ground Screw/Jumper
Settings
Determine the ground screw/jumper setting for your Kinetix 5700 drive
system power supply, iTRAK power supply, and Kinetix 5700 inverters.
Kinetix 5700 Drive System Power Supply
The Kinetix 5700 drive system power supply can be either 2198-Pxxx DC-bus
power supply or 2198-RPxxx regenerative bus supply.
DC-bus Power Supply
The 2198-Pxxx DC-bus power supply has a factory-installed ground screw for
grounded-wye power distribution. Table 65
summarizes the ground screw/
jumper settings for the 2198-Pxxx DC-bus power supply.
Regenerative Bus Supply
The 2198-RPxxx regenerative bus supply includes a factory-installed ground
jumper for grounded-wye power distribution. Table 66
summarizes the
ground jumper settings for the 2198-RPxxx regenerative bus supply.
Table 65 - Ground Screw Setting for the DC-bus Power Supply
Ground Configuration Example Diagram
2198-Pxxx
DC-bus Power Supply
Grounded (wye) Figure 72 on page 121
Ground screw installed (default setting)
(1)
(1) Ground screw is factory installed.
• Impedance grounded
• Corner grounded
•AC-fed ungrounded
Figure 73 on page 122
Figure 74 on page 122
Figure 75 on page 123
Remove ground screw/jumper
IMPORTANT
If you have grounded-wye power distribution in your facility, do not
remove the ground screw from the DC-bus power supply. Remove the
ground screw when using ungrounded, corner-grounded, or impedance-
grounded power.
Table 66 - Ground Jumper Setting for the Regenerative Bus Supply
Ground Configuration Example Diagram
2198-RPxxx
Regenerative Bus Supply
•Grounded (wye)
• Corner-grounded with isolation transformer
• Ungrounded with isolation transformer
Figure 76 on page 124
Figure 78 on page 126
Figure 79 on page 126
Ground jumper is factory
installed (default setting)
Impedance grounded Figure 77 on page 125
Remove ground jumper
(1)
(1) When the regenerative bus supply ground jumper is removed, it can be permanently stored in threaded holes at the bottom of
the chassis.
IMPORTANT
If you have grounded-wye power distribution in your facility, or corner-
grounded or ungrounded power with an isolation transformer, do not
remove the ground jumper from the regenerative bus supply. Remove
the ground jumper when using impedance-grounded power.