42 Rockwell Automation Publication 2198-UM002L-EN-P - October 2021
Chapter 2 Plan the Kinetix 5700 Drive System Installation
AC Line Filter Selection
An AC line filter is required to meet CE requirements. Install an AC line filter
for input power with 50 mm (1.97 in.) minimum clearance between the
2198-Pxxx DC-bus power supply or 2198-RPxxx regenerative bus supply.
Minimize the cable length as much as possible.
IMPORTANT
AC line filters are recommended only with grounded WYE power
configurations. For facility power configuration examples, see Input
Power Configurations for Kinetix 5700 Power Supplies on page 121.
Table 7 - AC Line Filter Selection
DC-bus Power Supply
Cat. No.
AC Line Filter
(1)
(2)
(3)
Cat. No.
Regenerative Bus Supply
Cat. No.
AC Line Filter
(1)
(2)
(4)
Cat. No.
2198-P031
2198-DBR20-F or
•2198-DB20-F
2198-RP088 2198-DBR40-F
2198-P070
•2198-DBR40-F or
•2198-DB42-F
2198-RP200 2198-DBR90-F
2198-P141
2198-P208
2198-DBR90-F or
2198-DB80-F
2198-RP263
2198-RP312
2198-DBR200-F
2198-P208 (2 in parallel)
2198-P208 (3 in parallel)
2198-DBR200-F or
2198-DB290-F
(1) The use of 2198-DBRxx-F line filters provide a maximum motor-power cable length of up to 1200 m (3937 ft). Maximum motor-power cable length with 2198-DBxx-F line filters is 400 m
(1312 ft).
Maximum motor-power cable length for 2198-P031 DC-bus power supplies when paired with 2198-DBxx-F or 2198-DBRxx-F line filters is with 400 m (1312 ft).
(2) See Chapter 5
on page 119 for more information on maximum cable lengths and how the use of 2198-DBRxx-F line filters affect ground screw/jumper settings. See Kinetix 5700, 5500, 5300,
and 5100 Servo Drives Specifications Technical Data, publication KNX-TD003
, for AC line filter specifications.
(3) When using 2198-DBRxx-F line filters with DC-bus power supplies, remove all inverter ground jumpers to reduce overall system leakage current.
(4) When using 2198-DBRxx-F line filters with regenerative bus supplies, remove all inverter ground jumpers to prevent permanent damage to the inverters.
IMPORTANT
Use 2198-DBxx-F line filters only as field replacements in existing installations that use DC-bus power supplies and
have inverter ground jumpers installed. Select 2198-DBRxx-F line filters for all new systems and remove inverter ground
jumpers. 2198-DBRxx-F line filters can also be used to replace existing 2198-DBxx-F line filters, but you must remove
the inverter ground jumpers.