364 Rockwell Automation Publication 2198-UM002L-EN-P - October 2021
Appendix B Upgrade the Drive Firmware
Use ControlFLASH Plus Software to Upgrade Your Drive Firmware
Follow these steps to select the Kinetix 5700 drive to upgrade.
1. Start ControlFLASH Plus software.
2. Click the Flash Devices tab. If the device is not already present in
Browsing from path:, complete these steps:
a. Click .
b. In the Network Browser dialog box, locate and select the device to
upgrade.
c. Click OK.
3. On the Flash Devices tab,
verify that the check box to the
left of the device is selected.
You can choose to select and upgrade the firmware for all drive
modules in your system. However, in this procedure only one
drive is selected for a firmware upgrade.