226 Rockwell Automation Publication 2198-UM002L-EN-P - October 2021
Chapter 6 Configure and Start the Kinetix 5700 Drive System
Sensorless Vector Method
1. Configure the General category and Motor category as shown in General
and Motor Categories on page 223.
2. Select the Frequency Control category.
3. From the Frequency Control Method pull-down menu, choose Sensorless
Vector.
4. Enter the Basic Volts/Hertz attribute values appropriate for your
application.
Default values are shown.
5. Click Apply.
6. Select the Parameter List category.
7. The Motion Axis Parameters dialog box appears.
8. From the Parameter Group pull-down menu, choose Frequency Control.