396 Rockwell Automation Publication 2198-UM002L-EN-P - October 2021
Appendix E Regenerative Bus Supply Sequence Operation
Sequence Operation of
Discharging
In the discharging sequence, the regenerative bus supply begins in the
RUNNING state and transitions to the STOPPED state following a Motion
Servo Off (MSF) command. If a Motion Axis Shutdown (MASD) command is
executed, the regenerative bus supply transitions to the SHUTDOWN state,
and a Motion Axis Shutdown Reset (MASR) command must be executed to
transition out of the SHUTDOWN state.
Figure 208 - Sequence Operation of Discharging - Enable Request Method
DC-bus Voltage
CIP Axis State
CONT_EN Output
Digital Input - Enable
Enable Request (MSO)
DC Bus Up
DC Bus Unload
Power Structure Enabled
Tracking Command
STOPPED
START INHIBITED
SHUTDOWN
RUNNING
Shutdown Request (MASD)