Rockwell Automation Publication 2198-UM002L-EN-P - October 2021 413
Appendix F Motor Control Feature Support
Figure 225 - Motor Manufacturer Performance Data Sheet
Motor>Model Category
From the Motor>Model category you can enter additional motor nameplate or
datasheet values (phase-to-neutral parameters) for induction motors.
The Motor>Model parameters are used in closed-loop induction-motor control
mode, sensorless vector control mode, and when FluxUp is enabled, and are
estimated automatically by the Logix Designer application based on the motor
nameplate data. You can also enter these parameter values directly from the
motor nameplate/datasheet or indirectly by running a Motor>Analyzer test.
Figure 226 - Phase-to-Neutral Parameters
CERTIFICATION DATA SHEET
TYPICAL MOTOR PERFORMANCE DATA
HP kW SYNC. RPM F.L. RPM FRAME ENCLOSURE KVA CODE DESIGN
1 .75 1800 1725 56C T E NV P A
PH Hz VOLTS FL AMPS START TYPE DUTY INSL S.F. AMB°C ELEVATION
3 60 230/ 3/ 1. 5 INV E R T E R ONL Y CONT INUOUS F 3 1. 0 40 3300
FUL L L OAD EFF: 84 3/4 L OAD EFF: 82.5 1/2 L OAD E FF: 78.5
GTD. EFF ELEC. TYPE NO LOAD AMPS
FUL L L OAD PF: 75 3/4 L OAD PF: 65.5 1/2 L OAD PF: 51 81.5 SQ CAGE INV DUTY 2 / 1
F.L. TORQUE LOCK ED ROTOR AMPS L.R. TORQUE B.D. TORQUE F.L. RISC
3 L B -F T 30 / 15 10. 8 L B -F T 360% 15 L B -F T 500% 65
SOUND PR E SSUR E
@ 3 FT.
SOUND POWER ROTOR WK ^2 MAX. WK ^2 SAFE STALL TIME
STAR TS /
HOUR
APPROX.
MOTOR WGT
62 dB A 72 dBA 0.11 L B-FT ^2 0 L B-FT ^2 0 SE C. 0 42 L BS.
EQUIVALENT WYE CKT.PARAMETERS (OHMS PER PHASE)
R1 R2 X1 X2 XM
8. 378 5. 6232 10. 7068 9.9116 278. 036
RM ZREF XR TD TD0
11132. 8 284 1. 7 0. 0071 0. 136
460
IMPORTANT
If you do not know the Stator Leakage, Rotor Leakage, Stator
Resistance, Rated Flux Current, and system inertia, you can run
the static motor test and Autotune procedure to determine the
parameter values.