72 Rockwell Automation Publication 2198-UM002L-EN-P - October 2021
Chapter 2 Plan the Kinetix 5700 Drive System Installation
Figure 40 - External Shunt Resistor Mounted Inside the Drive System Enclosure
External Active Shunt Modules
Observe these guidelines when mounting external active shunt outside the
drive system enclosure:
Mount the shunt module so that wiring routes in the very dirty zone
inside the drive system enclosure.
Keep unshielded wiring as short as possible, not to exceed 3 m (9.8 ft).
Keep shunt wiring as flat to the cabinet as possible.
D
D
C
VD
C
VD
MOD
NET
2
1
I/O-A I/O-B
UFB-A UFB-B
D+
D-
MF-A MF-B
D+
D-
MOD
NET
2
1
1
4
I/O
MOD
NET
2
1
I/O-A I/O-B
UFB-A UFB-B
D+
D-
MF-A MF-B
D+
D-
MOD
NET
2
1
I/O-A I/O-B
UFB-A UFB-B
D+
D-
MF-A MF-B
D+
D-
MOD
DC BUS
C
D
16
510
16 1616 1616
50 mm
(1.97 in.)
Dirty Wireway
Clean Wireway
Motor Cables
Enclosure
No sensitive
equipment within
150 mm (6.0 in.).
Shunt Power Wiring Methods:
Twisted pair in conduit (1st choice).
Twisted pair, two twists per foot (min) (2nd choice).
Circuit
Protection
Digital Inputs and
Ethernet Cables
Route motor cables
in shielded cable.
Route registration and communication
signals in shielded cables.
Kinetix 5700 Servo Drive System
24V DC
Power Supply
AC Line Filter
(required for CE)
Module Status
76 mm (3.0 in.)
clearance (min) below, left,
and right of the shunt resistor.
Safety Cable
(hardwired safety only)
150 mm (6.0 in.)
clearance (min) above the
shunt resistor.
Very Dirty Filter/AC Input
Connections Segregated
(not in wireway)