Figure 3-97
Example of the Threshold Value of the Definite Time-Overcurrent Protection (Edit Mode:
Percent)
When switching over to the secondary view, the result should be the following value:
1500 A/(1000 A/1 A) = 1.5 A
System Functions
3.9 General Notes for Setting the Threshold Value of Protection Functions
158 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017