Figure 3-98
Example of the Threshold Value of the Definite Time-Overcurrent Protection (Edit Mode:
Secondary)
If you only want to work in the secondary view, DIGSI 5 supports you if the transformer ratio changes during
the project phase.
In the example, the current-transformer ratio changes from 1000 A/1 A to 1000 A/5 A. Change the secondary
rated current of the current transformer in the setting sheet of the transformer data from 1 A to 5 A (Edit
mode: Secondary). If you change the transformer data, a window will appear (see the following figure) that
will ask you for the action desired.
System Functions
3.9 General Notes for Setting the Threshold Value of Protection Functions
SIPROTEC 5, High-Voltage Bay Controller, Manual 159