Reset of Trip Command
[loauslbe-190912-01.tif, 1, en_US]
Figure 5-35
Reset of Trip Command
Once a trip command is issued, it is stored (see Figure 5-34).
You determine the criteria for resetting a trip command that has been issued with the parameter Reset of
trip command.
with dropout
The trip command is reset if the function that initiated tripping terminates its operate indication. This
occurs typically with dropout. Resetting the trip command takes place regardless of verification of the
circuit-breaker condition.
with I<
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
SIPROTEC 5, High-Voltage Bay Controller, Manual 233
C53000-G5040-C015-9, Edition 11.2017