EasyManua.ls Logo

Siemens 6MD86 - Page 232

Siemens 6MD86
1256 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
All other cases result in 3-pole operate.
3-Pole Coupling
3-pole coupling describes the situation when the trip logic decides to execute 3-pole tripping despite the pres-
ence of a 1-pole operate indication.
This may be the case under the following circumstances:
The Automatic reclosing function cannot execute a 1-pole cycle. This is expressed by the cleared signal
79 permits 1-pole trip.
If an upstream device has caused 1-pole tripping and the device in question detects this pole as open (via
the process monitor in the Line protection function group) and the device in question detects a fault in
another conductor
If 1-pole tripping reoccurs within 50 ms after an instance of 1-pole tripping has been cleared
If the permission for 1-pole tripping is canceled by the AR (internal or external) after a cleared 1-pole trip
(during the 1-pole pause)
By default, 3-pole coupling is carried out based on the cumulative operate indication. Optionally, the group
pickup indication can also be taken into account (parameter 3-pole coupling). In this case, every multi-
phase pickup results in a 3-pole coupling, including pickups of different phases from different stages/func-
tions.
2-Phase Short-Circuits
For 2-pole faults, you set the behavior with the parameter Trip at 2ph short circuit.
3-pole
Tripping is executed in the event of 2-pole faults.
1-pole, leading phase
1-pole tripping takes place in the event of 2-pole faults without grounding. The leading phase is tripped
(for more information, see Table 5-6). In the event of a BC fault, for example, pole B is tripped. 3-pole
tripping takes place in the event of 2-pole faults with grounding.
1-pole, lagging phase
1-pole tripping takes place in the event of 2-pole faults without grounding. The lagging phase is tripped.
In the event of a BC fault, for example, pole C is tripped. 3-pole tripping takes place in the event of 2-pole
faults with grounding.
Coupling Table
The following table shows the coupling table for Figure 5-34. This table also explains its impact on 2-phase
faults.
Table 5-6
Coupling
Input Output
Impact of the parameter Trip at 2ph short circuit
3-pole 1-pole, leading phase 1-pole, lagging phase
A B C Groun
d
A B C A B C A B C
1 0 0 0 1 0 0 1 0 0 1 0 0
0 1 0 0 0 1 0 0 1 0 0 1 0
0 0 1 0 0 0 1 0 0 1 0 0 1
1 1 0 0 1 1 1 1 0 0 0 1 0
0 1 1 0 1 1 1 0 1 0 0 0 1
1 0 1 0 1 1 1 0 0 1 1 0 1
1 1 1 0 1 1 1 1 1 1 1 1 1
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
232 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017

Table of Contents

Other manuals for Siemens 6MD86

Related product manuals