If the >Start signal is active and no release signal is present after elapse of the settable supervision time for
the starting signal, the pickup is blocked and an indication to this effect is output. The Health signal changes
to the state Warning. The blocking is reset with the dropout of the starting signal.
The binary input signals only take effect if the binary inputs are activated for at least 10 ms (SW filter, see
Figure 7-7).
[logikext-070611-02.tif, 2, en_US]
Figure 7-7
External Start of the Circuit-Breaker Failure Protection Function, Logic of the 3-Pole Circuit
Breaker
Protection and Automation Functions
7.1 Circuit-Breaker Failure Protection
520 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017