Addr. Parameter C Setting Options Default Setting
_:751:8 Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:751:3 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:4 Definite-T 1:Dropout
ratio
0.90 to 0.99 0.95
_:751:101 Definite-T 1:Dropout
delay
0.00 s to 60.00 s 0.00 s
_:751:6 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR off/n.rdy
_:751:28 Definite-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:751:35 Definite-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:751:29 Definite-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:751:36 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:14 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:20 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 2
_:751:30 Definite-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:751:37 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:15 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:21 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: AR cycle 3
_:751:31 Definite-T 1:Effected by
AR cycle 3
•
no
•
yes
no
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual 643
C53000-G5040-C015-9, Edition 11.2017