Addr. Parameter C Setting Options Default Setting
_:751:38 Definite-T 1:Stage
blocked
no
yes
no
_:751:16 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:22 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: AR cycle>3
_:751:32 Definite-T 1:Effected by
AR cycle gr. 3
no
yes
no
_:751:39 Definite-T 1:Stage
blocked
no
yes
no
_:751:17 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:23 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.s: Cold load PU
_:751:33 Definite-T 1:Effect. b.
cold-load pickup
no
yes
no
_:751:40 Definite-T 1:Stage
blocked
no
yes
no
_:751:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:24 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: bin.input
_:751:34 Definite-T 1:Effected by
binary input
no
yes
no
_:751:41 Definite-T 1:Stage
blocked
no
yes
no
_:751:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 50 Irated 0.010 A to 35.000 A 1.200 A
5 A @ 50 Irated 0.05 A to 175.00 A 6.00 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.200 A
5 A @ 1.6 Irated 0.002 A to 8.000 A 6.000 A
_:751:25 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
644 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017