Addr. Parameter C Setting Options Default Setting
Dyn.s: Cold load PU
_:8131:33 Definite-T 1:Effect. b.
cold-load pickup
•
no
•
yes
no
_:8131:40 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:8131:18 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:24 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
Dyn.set: bin.input
_:8131:34 Definite-T 1:Effected by
binary input
•
no
•
yes
no
_:8131:41 Definite-T 1:Stage
blocked
•
no
•
yes
no
_:8131:19 Definite-T 1:Threshold 1 A @ 100 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 100 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 50 Irated 0.030 A to 35.000 A 1.500 A
5 A @ 50 Irated 0.150 A to 175.000 A 7.500 A
1 A @ 1.6 Irated 0.001 A to 1.600 A 1.500 A
5 A @ 1.6 Irated 0.005 A to 8.000 A 7.500 A
_:8131:25 Definite-T 1:Operate
delay
0.00 s to 60.00 s 0.30 s
General
_:8132:1 Definite-T 2:Mode
•
off
•
on
•
test
off
_:8132:2 Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:8132:105 Definite-T 2:Directional
mode
•
forward
•
reverse
forward
_:8132:8 Definite-T 2:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:8132:107 Definite-T 2:Non-direc-
tional pickup
•
no
•
at volt.< & mem.empty
at volt.< &
mem.empty
_:8132:104 Definite-T 2:Directional
comparison
•
no
•
yes
no
_:8132:106 Definite-T 2:Release via
input signal
•
no
•
yes
no
_:8132:10 Definite-T 2:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:8132:26 Definite-T 2:Dynamic
settings
•
no
•
yes
no
_:8132:27 Definite-T 2:Blk. w.
inrush curr. detect.
•
no
•
yes
no
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
676 SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017